Program blocks
5.4 Blocks for logical functions
Parameters
Parameters
Input parameters
En
Input 1 ... Input 4
Output parameters
Output
5.4.2

Logical OR

Function
At least one input must be activated so that the block is processed.
The output of the block is set to 1, when at least one configured input is set to 1.
If no input is set to 1, the output is set to 0.
256
Range of values
Description
Enable parameter, see section Often used parameters
(Page 252).
The values of the inputs are processed by the block
Digital input /
function.
output / bit
memory
True / False
STATUS_ERROR
Tag in which the value calculated by the block is output.
Digital output / bit
memory
Operating Instructions, 06/2019, C79000-G8976-C382-06