Configuration (WBM)
4.19 Tags
Logging
See section Configuration of the tags , general parameters (Page 179).
Additional value
● Mean value generation
Select a degree of mean value generation over several update cycles:
– None
– Weak
– Medium
– Strong
Diagnostics messages
● Wire break
If wire break is detected at life-zero inputs, if the option is enabled a message is entered
in the diagnostics buffer
With other measured variables, the option has no effect.
● Outside the measuring range
If the option is enabled, a message is entered in the diagnostics buffer when
under/overvoltage or under overcurrent is detected.
With temperature measurements, the option has no effect.
For over/undershoot ranges or over/underflow, refer to the section "Measuring ranges".
Regardless of configured diagnostics messages, the LED of an input (Aix) is lit red with wire
break, over/undervoltage or under/overcurrent.
188
No mean value generation
Mean value generation over 2 cycles
Mean value generation over 4 cycles
Mean value generation over 8 cycles
Operating Instructions, 06/2019, C79000-G8976-C382-06
RTU303xC