Siemens Simatic RTU303xC Series Operating Instructions Manual page 22

Telecontrol rtu
Table of Contents

Advertisement

Application and functions
1.3 Modes and operating modes
Logging
In the "Logging" mode the RTU has no communications partner in the master station.
Instead, the RTU stores the process data.
This operating mode is adopted when logging must be enabled in the WBM in "Operating
mode".
In the "Logging" mode, the RTU requires an SD card where it can store the process data.
The stored process data can be read out from the SD card or sent via the mobile wireless
network or the LAN interface and an external router. Cyclic sending is possible by e-mail or
FTP. You can load the data on a PC via the WBM.
Operating modes
The RTU can adopt the following operating modes:
● Sleep mode
● Update mode
● Communication mode
● Service mode
Sleep mode
In the energy-saving standard operating mode the updating of the inputs and outputs, the
communications functions, the LEDs and the self check function (see section Other services
and properties (Page 34)) of the RTU are turned off.
The RTU interrupts the sleep mode in the following situations:
● Pressing the button "WKUP" and changing to the service mode
● Configured change to the update mode (WBM > Operating mode)"
With the inputs, other specific update cycles can be configured (WBM > "Tags").
● Configured change to the communication mode (WBM > Operating mode)"
● Pending diagnostics message with configured change to the communication mode (WBM
> "Diagnostics" > "Notifications")
● Cyclic interruption of the sleep mode to fetch a wake-up SMS (WBM > "Operating mode")
● Occurrence of certain events:
– Creating a new log file with a configured change to the communication mode to
– Further events, refer to the section "Update mode".
In the "TeleControl" mode, the RTU in sleep mode has the greatest energy-saving potential
when using the "TeleControl Basic" protocol.
Update mode
The update mode is controlled by the configurable update cycle, refer to the section
Operating modes (Page 166).
22
transfer the old log file
Operating Instructions, 06/2019, C79000-G8976-C382-06