Program blocks
5.9 Blocks for messages
Parameters
Send Immediately
Function parameters
File
Compressed and en-
crypted
Server path
Append
Output parameters
Done
Error
314
Tag type / range of
Description
values
True / False
With the setting "True" when entering an FTP trans-
fer in the transfer list the communication mode is
Digital input / out-
started immediately if the RTU is not already in the
put / bit memory
communication mode. The transfer list is processed
STATUS_ERROR
immediately. FTP transfers saved previously in the
transfer list are also processed.
With the setting "Not used" or "False", the FTP
transfer is kept in the transfer list until the RTU is in
the communication mode for some other reason.
This can be a planned communication mode or
another FTP transfer with the setting "Send imme-
diately" = TRUE).
This parameter specifies which data is transferred
Entire diagnostics
to the FTP server during the FTP transfer.
buffer
Current log file
Current process
image
ON / OFF
Transfers the file as a compressed ZIP archive. As
an option, the ZIP archive can also be encrypted
(see WBM: "Services > FTP").
Path 1 .. 8
Selection of one of the FTP server paths". specified
in "Services > FTP
If you do not make a selection (not used) the stand-
ard path of the FTP server will be used.
ON / OFF
With the setting "ON" the transferred file is append-
ed to an existing file of the same name on the serv-
er.
With the setting "OFF" an existing file that may be
on the FTP server is replayed.
If the file is transferred as a ZIP archive, the option
"Append" cannot be used.
Status display:
Digital output / bit
memory
Error display:
Digital output / bit
memory
0: FTP transfer could not be entered in the
transfer list. The list is possibly full.
1: FTP transfer successfully entered in the
transfer list.
0: Block processing completed without errors
1: Block processing aborted with an error.
FTP transfer could not be saved. See also sec-
tion Often used parameters (Page 252).
Operating Instructions, 06/2019, C79000-G8976-C382-06