Chapter 5 Specification of Parameters
Table5-2.
Accel/Decel time
determinant 2
OFF
OFF
ON
ON
 ATTENTION:
When the drive is running under simple PLC, the Accel time and Decel time are determined
by simple PLC related parameters, not by the DI terminals. See Group P52 for details.
When Accel/Decel of broken-line style is selected, Accel/Decel time is automatically
switched to Accel/Decel time 1 and 2 according to switching frequency (P12.13 and
P12.14).
Under this circumstance, Accel/Decel time selection terminals are disabled.
Decel time for
P12.09
emergency stop
In case of emergency stop via multifunction MF key on keypad (MF key has been set to
emergency stop 1 through parameter P70.00), or via DI terminal "emergency stop", Decel is
conducted according to this time. This parameter sets the rate of Decel for speed decrease,
similar with P12.01~P12.08.
P12.10
Jog Accel time
P12.11
Jog Decel time
P12.10 and P12.11 set the rate of Accel/Decel of Jog, similar with P12.01~P12.08.
P12.12
Accel/Decele curve
0: Linear Accel/Decel
Outputs frequency increases or decreases with a constant rate as shown in Fig.5-8.
Table5-2
Accel/Decel time
determinant 1
OFF
ON
OFF
ON
Range: 0s~60000s
Range: 0s~60000s
Range: 0s~60000s
Range: 0~4
- 88 -
E5 User Manual
Accel/Decel time
Accel/Decel time 1(P12.01,
P12.02)
Accel/Decel time 2(P12.03,
P12.04)
Accel/Decel time 3(P12.05,
P12.06)
Accel/Decel time 4(P12.07,
P12.08)
Factory default:
Factory default:
Factory default:
Factory default: 0
6.0s
6.0s
6.0s