E5 User Manual
Setting
Corresponding function
Frequency higher than FDT 1
10
Frequency higher than FDT 2
11
Reserved
12
Torque being constrained
13
(speed control mode)
Fault output
14
Alarm output
15
Drive (motor) overloaded
16
alarm
0: No output
Output terminal is disabled, and there is no output.
1: Drive undervoltage
When DC bus voltage is lower than the level of undervoltage, output ON signal and LED
keypad displays "LoU".
2: Drive running preparation completed
The output of ON signal indicates that the drive is free of fault, the bus voltage is normal, and
the running prohibition terminal is disabled. Under this circumstance, run command is
acceptable.
3: Drive is running
The output is ON when the drive is running, and output is OFF when drive stopped.
4: Drive in 0Hz running (no output at stop)
When be running at 0Hz, this corresponding terminal outputs ON signal. No ON signal will be
output at stop.
5: Drive in 0Hz running (output at stop)
Under V/f control, Outputs ON signal when is running at 0Hz and also outputs ON signal at
stop.
6: Running direction
Outputs OFF signal under forward running and outputs ON signal under reverse running.
7: Frequency attained
When the deviation of output frequency from command frequency is less than the value of
P21.14 (Detective width of frequency attained), outputs ON.
8: Upper limit frequency attained
When output frequency attains P10.09 (upper limit frequency), outputs ON.
Chapter 5 Specification of Parameters
Setting
Corresponding function
Contracting brake control
27
Reserved
28
Reserved
29
PLC step completed
30
PLC cycle completed
31
Wobble frequency attains to upper
32
or lower limit frequency
Reserved
33~99
- 107 -