Best E5 Series User Manual page 56

High-performance frequency inverter
Table of Contents

Advertisement

Chapter 4 List of Parameters
Param.
Designation
P50.00
PID setting
P50.01
PID digital setting
P50.02
PID feedback
P50.03
PID adjustment
PID positive and
P50.04
negative adjustment
Filtering time of PID
P50.05
setting
Filtering time of PID
P50.06
feedback
Filtering time of PID
P50.07
output
P50.08
Proportional gain Kp1
P50.09
Integration time Ti1
P50.10
Differential time Td1
P50.11
Proportional gain Kp2
P50.12
Integration time Ti2
P50.13
Differential time TP32
P50.14
PID parameter switch
Scope
0: P50.01 digital setting
1: AI1
2: AI2
3: Reserved
4: X6/DI pulse input
5: Communication
0.0%~100.0%
0: AI1
1: AI2
2: Reserved
3: AI1+AI2
4: AI1-AI2
5: Max {AI1, AI2}
6: Min {AI1, AI2}
7: X6/DI pulse input
8: Communication
Unit's place: output frequency
0: Must be the same direction as
setting running direction
1: Opposite direction allowed
Decade: integration selection
0: Integral continued when
frequency attains upper/lower
frequency
1: Integral stopped when
frequency attains upper/lower limit
0: Positive adjustment
1: Negative adjustment
0.00s~60.00s
0.00s~60.00s
0.00s~60.00s
0.0~100.0
0.0s~100.0s
0.0s~100.0s
0.0~100.0
0.0s~100.0s
0.0s~100.0s
0: No switch, determined by
- 52 -
E5 User Manual
Factory
Attr
Default
0
50.0%
0
11
0
0.00s
0.00s
0.00s
2.0
1.0s
0.0s
2.0
1.0s
0.0s
0

Advertisement

Table of Contents
loading

Related Products for Best E5 Series