Chapter 4 List of Parameters
Param.
Designation
Reserved
P33.21
Autotuning of motor 2
P33.22
Overload protection
P33.23
mode of motor 2
Overload protection
P33.24
detection time of motor 2
Input source of
temperature transducer
P33.25
signal of motor 2
Thermal protection
threshold of temperature
P33.26
transducer of motor 2
V/f curve setting
P34.00
P34.01
V/f frequency value f3
P34.02
V/f voltage value V3
P34.03
V/f frequency value f2
P34.04
V/f voltage value V2
P34.05
V/f frequency value f1
P34.06
V/f voltage value V1
P34.07
V/f frequency value f0
P34.08
V/f voltage value V0
P34.09
Torque boost
P34.10
Slip compensation gain
P34.11
Droop control
P34.12
Current limitation mode
Reserved
0: No identification
1: Static identification of async
motor
2: Rotating identification of async
motor
0: No protection
1: Judged from motor current
2: Judged from temperature
transducer
0.1min~15.0min
0: AI1
1: AI2
2: Reserved
0.00V~10.00V
Group P34 V/f Control Parameters of Motor 2
0: Linear V/f
1: Multi-stage V/f (P31.01~P31.08)
2: 1.2nd power
3: 1.4th power
4: 1.6th power
5: 1.8th power
6: 2.0nd power
7: V/f separated mode 1
8: V/f separated mode 2
0.00Hz~rated frequency of motor
0.0%~100.0%
P34.05~ P34.01
0.0%~100.0%
P34.07~ P34.03
0.0%~100.0%
0.00Hz~ P34.05
0.0%~100.0%
0.0%~30.0%
0.0%~400.0%
0.00Hz~mximum frequency
0: Disabled
1: Set by P34.13
Scope
- 46 -
E5 User Manual
Factory
Attr
Default
Reserved
0
1
5.0min
0
10.00V
0
50.00Hz
100.0%
0.00Hz
0.0%
0.00Hz
0.0%
0.00Hz
0.0%
0.0%
100.0%
0.00Hz
1