3.4 Parameter Modification Method

If parameters need modification, first you shall enter into the function code which requires
modification, then reset the parameter. Refer to details as below:
Sequence
1
2
3
4
5
6
7
Note: When setting parameters, pressing "ESC" key can exit parameter setting state and back
to standby mode.
3.5 Commissioning
3.5.1 Important inspection Before Running
 Whether exists wrong wiring, especially check whether the power supply is wrongly
connected to U.V.W terminal;
 Please pay attention: power supply should be input from R.S.T(L.N) terminals;
 Whether there are metal chips or wires, which may cause short-circuit, left on inverter base
board and wiring terminals;
 Whether screws are tightly screwed, whether connectors are loose;
Rotating Speed
ON: Present displayed parameter is rotating speed;
Indication
Flash: Present displayed is set rotating speed.
Percentage
ON: Present displayed parameter is percentage.
Indication
Operation
Enter into parameter menu, e.g. P00-00, inverter
displays present parameter's first level menu.
Adjust to the parameter which requires modification,
e.g. P00-00.
Adjust to the required parameter code, e.g. P10-00.
Inverter displays the value of present parameter, e.g.
"0".
Adjust to the required value, e.g. "1".
Confirm this operation, save information.
Exit parameter setting condition, back to standby or
running condition.