Chapter 5 Specification of Parameters
0: Master frequency command
Output frequency of drive is determined by master frequency command source P10.01.
Refer to parameters P10.01 and P10.02 for further information.
1: Master & auxiliary computation result
Frequency command is the result of master & auxiliary computation. The master & auxiliary
computation relation is determined by P10.07. Main command is set by P10.01, while
auxiliary is et by P10.03
2: Switch between master frequency command, and auxiliary frequency command
When P10.00 is set to 2, the switch between master frequency command, and master &
auxiliary computation result can be realized through digital input terminal "frequency
command switchover". When terminal "frequency command switchover" is invalid, command
frequency of the drive will be determined by P10.01. When terminal "frequency command
switchover" is valid, command frequency of the drive will be determined by P10.03 (Auxiliary
frequency command source).
3: Switch between master frequency command, and master & auxiliary computation result
When P10.00 is set to 3, command frequency will de determined by master frequency
command, or master & auxiliary computation result through digital input terminal "frequency
command switchover". When terminal "frequency command switchover" is invalid, command
frequency is determined by P10.01 (master frequency command source). When terminal
"frequency command switchover" is valid, command frequency is determined by master &
auxiliary computation result. The master & auxiliary computation relation is determined by
P10.07.
4: Switch between auxiliary frequency command, and master & auxiliary computation result
When P10.00 is set to 4, command frequency will de determined by auxiliary frequency
command, or master & auxiliary computation result through digital input terminal "frequency
command switchover". When terminal "frequency command switchover" is invalid, command
frequency is determined by P10.03 (auxiliary frequency command source). When terminal
"frequency command switchover" is valid, command frequency is determined by master &
auxiliary computation result. The master & auxiliary computation relation is determined by
P10.07.
Master frequency
P10.01
command source
0: Digital setting (P10.02) + keypad ∧/∨ adjustment
When the drive is powered up, the value of P10.02 is taken as the master frequency
command which can be adjusted through ∧/∨ keys on keypad no matter the drive is
running or in stop.
 ATTENTION:
Frequency adjustment via keypad ∧/∨can be cleared through terminal "UP/DOWN (including ∧/
Range: 0~9
- 74 -
E5 User Manual
Factory default:
0