E5 User Manual
BIT1: Reserved
BIT2: Reserved
BIT3: Reserved
Thousands place: Reserved
LED displayed setting on
P71.02
Sets LED displayed parameters on stop status. When a number of parameters are selected,
skim-through could be realized via key >> on keypad.
0: Displayed disabled
1: Displayed enabled
Unit's place
BIT0: Command frequency (Hz)
BIT1: Bus voltage (V)
BIT2: Input terminal status
BIT3: Output terminal status
Decade
BIT0: AI1 (V)
BIT1: AI2 (V)
BIT2: RESERVED (V)
BIT3: Reserved
Hundreds place
BIT0: PID setting (%)
BIT1: PID feedback (%)
BIT2: Set length (m)
BIT3: Actual length (m)
Thousands place
BIT0: Running linear speed (m/s)
BIT1: Set linear speed (m/s)
BIT2: External count value
BIT3: DI
Note: when this function code is set to 0000, the set frequency would be displayed as default
(Hz).
Example:
To display command frequency, bus voltage, AI1 sampled value, set length and external count value,
P71.02 should be: 0100 0100 0001 0011, i.e. set P71.02 to 4413.
P71.03
Linear speed coeff
This coefficient is used for calculation of linear speed.
Running linear speed = motor running speed x P71.03
stop status
Chapter 5 Specification of Parameters
Range: 0000~FF7F
Range: 0.1%~999.9%
- 169 -
Factory default:
0003
Factory default:
100.0%