E5 User Manual
the running will be continued in accordance with the memorized status.
Hundreds place: started mode
0: Run from the first step "multi-step frequency 0"
When restarted after stop, the drive will start to run from "step 0".
1: Continue to run from the step of stop (or fault)
At the moment drive stop, the drive automatically records the running time of current step.
When restarted, the drive will gets into this step, continue to run the remanent time with the
frequency of this step.
2: Continue to run from the step and frequency at which the running stopped (or fault occurred)
At the moment of stop, the drive not only records the running time of current step, but also
records the running frequency at the moment of stop. When restarted, it will restore the
running frequency that was recorded at the moment of stop, and then continue to run the
remanent step.
Thousands place: unit of simple PLC running time
0: Second
1: Minute
Sets the unit of running time and Accel/Decel time of simple PLC.
Setting of multi-step 0
P52.01
Unit's place: frequency command
Sets the frequency command of step 0 of simple PLC.
0: Multi-step frequency 0 (P51.02)
1:AI1
2:AI2
3: Reserved
4: X6/DI pulse input
5: Process PID output
6: Multi-step frequency
7: Communication
Decade: running direction
Sets the running direction for step 0 of simple PLC.
0: Forward
1: Reverse
2: Determined by run command
Hundreds place: Accel/Decel time option
Sets the Accel/Decel time step 0.
0: Accel/Decel time 1
1: Accel/Decel time 2
Chapter 5 Specification of Parameters
Range: 000~327
- 155 -
Factory default:
000