Best E5 Series User Manual page 156

High-performance frequency inverter
Table of Contents

Advertisement

Chapter 5 Specification of Parameters
3:AI1
4:AI2
5: Reserved
6: X6/DI pulse input
7: Process PID output
8: Communication
At most 16-step of frequency can be set through the combination of "multi-step frequency
terminals 1~4" of digital input. Multi-step frequency 2~15 are only digital setting while a number
of setting sources can be selected for multi-step frequency 0~1. Parameter value of P51.00
determines command source of step 0.
Frequency
P51.01
source of multi-step 1
0: Digital setting P51.03
1: Digital setting P10.04 + keypad ∧/∨ adjustment
2: Digital setting P10.04 + terminal UP/DOWN adjustment
3:AI1
4:AI2
5: Reserved
6: X6/DI pulse input
7: Process PID output
8: Communication
At most 16-step of frequency can be set through the combination of "multi-step frequency
terminals 1~4" of digital input. Multi-step frequency 2~15 are only digital setting while a number
of setting sources can be selected for multi-step frequency 0~1. Parameter value of P51.01
determines command source of step 1.
P51.02
Multi-step frequency 0
P51.03
Multi-step frequency 1
Multi-step frequency 2
P51.04
P51.05
Multi-step frequency 3
P51.06
Multi-step frequency 4
P51.07
Multi-step frequency 5
command
Lower limit frequency ~ upper
Lower limit frequency ~ upper
Lower limit frequency ~ upper
Lower limit frequency ~ upper
Lower limit frequency ~ upper
Lower limit frequency ~ upper
Range: 0~8
limit frequency
limit frequency
limit frequency
limit frequency
limit frequency
limit frequency
- 152 -
E5 User Manual
Factory default: 0
Factory default:
0.00Hz
Factory default:
0.00 Hz
Factory default:
0.00 Hz
Factory default:
0.00 Hz
Factory default:
0.00 Hz
Factory default:
0.00 Hz