E5 User Manual
P52.32
Running time of step 15
Sets the running time for step 15 of simple PLC. The time unit is set by thousand's place of
P52.00.
 ATTENTION:
Digital input terminals "simple PLC paused", "simple PLC disabled" and "simple PLC stop
memory clear" can be used during the running of simple PLC. See specification of digital
input of Group P20 for details.
Group P53 Wobble Frequency and Fixed Length Count
Wobble frequency function is usually used in textile and chemical fiber industries where
traverse motion is required. Wobble frequency control process is as follows: accelerate to the
pre-frequency of wobble frequency function according to the current Accel time. Maintain this
frequency for a period of time and run to center frequency of wobble frequency according to the
current Accel/Decel time (i.e. the set frequency set by parameter Group 10). Then run in a
cyclic manner according to wobble frequency amplitude, hopping frequency, wobble frequency
cycle time, and frequency ramp up time. When a stop command is given, the drive will ramp
down to stop according to the set Decel time
Wobble frequency function setting
P53.00
0: Wobble frequency function disabled
1: Wobble frequency function enabled
Wobble frequency running setting
P53.01
Unit's place: started method
0: Automatically
Run at pre-frequency of wobble frequency set by P53.02, maintain Pre-frequency holding
time set by P53.03, and then automatically get into wobble frequency running.
1: Started by terminal
Digital input terminal "start wobble frequency" controls the running of wobble frequency.
When terminal inputs ON, the drive gets into wobble frequency running. When terminal
inputs OFF, the drive exits wobble frequency and runs at pre-frequency of wobble frequency.
Under this mode, Pre-frequency holding time is enabled.
Decade: amplitude control
0: Relative to center frequency
Chapter 5 Specification of Parameters
Range: 0.0~6000.0s(min)
Range: 0~1
Range: 0000~1111
- 161 -
Factory default:
0.0s
Factory default: 0
Factory default:
0000