E5 User Manual
Param.
Designation
P52.01
Setting of multi-step 0
P52.02
Running time of step 0
P52.03
Setting of step 1
Scope
2: Repeat cycles
Decade: power loss memory
0: Memory disabled on power loss
1: Memory enabled on power loss
Hundreds place: started mode
0: Run from the first step "multi-step
frequency 0"
1: Continue to run from the step of
stop (or fault)
2: Continue to run from the step and
frequency at which the running
stopped (or fault occurred)
Thousands place: unit of simple PLC
running time
0: Second (s)
1: Minute (min)
Unit's place: frequency command
0: Multi-step frequency 0 (P51.02)
1: AI1
2: AI2
3: Reserved
4: X6/DI pulse input
5: Process PID output
6: Multi-step frequency
7: Communication
Decade: running direction
0: Forward
1: Reverse
2: Determined by run command
Hundreds place: Accel/Decel time
option
0: Accel/Decel time 1
1: Accel/Decel time 2
2: Accel/Decel time 3
3: Accel/Decel time 4
0.0s(min)~6000.0s(min)
Unit's place: frequency setting
0: Multi-step frequency 1 (P51.03)
1~7: Same as P52.01
Decade: running direction (same as
P52.01)
Hundreds place: Accel/Decel time
- 55 -
Chapter 4 List of Parameters
Factory
Attr
Default
000
0.0s
000