Best E5 Series User Manual page 126

High-performance frequency inverter
Table of Contents

Advertisement

Chapter 5 Specification of Parameters
Sampling value of
P24.05
calibration point 1 of AI2
Input value of calibration
P24.06
point 1 of AI2
Sampling value of
P24.07
calibration point 2 of AI2
Input value of calibration
P24.08
point 2 of AI2
P24.09
Reserved
P24.10
Reserved
P24.11
Reserved
P24.12
Reserved
Take AI2 for example, automatic correction is as follows
1) Set P24.00 to 2 in stop status and press ENT key to confirm. In this way, AI2 is
selected as correction channel.
2) Input a relatively low analog voltage (e.g. about 1V) via AI2 terminal, and input the
theoretical value of this analog voltage by P24.06 after the stabilization of this voltage
input, and then press ENT key to confirm.
3) Input a relatively high analog voltage (e.g. about 9V) via AI2 terminal, and input the
theoretical value of this analog voltage by P24.08 after the stabilization of this voltage
input, and then press ENT key to confirm.
4) Upon the successful correction, P24.00 parameter will be restored to zero.
 ATTENTION:
Set the theoretical value or actual value of analog voltage in P24.06 and P24.08. This value
can be either the set value of analog output of peripheral equipment, or the actual
voltage value of analog input measured by a multimeter or other instruments.
P24.05 and P24.07 are the sampling values of analog input voltage. These values is for
reference only. Do not write the value of P24.05 directly into P24.06, or write the value
of P24.07 directly into P24.08.
Group P30 Parameters of Motor 1
When motor 1 is selected as current load motor, please set motor parameters in Group P30.
P30.00
Type of motor 1
0: Ordinary asynchronous motor
1: Variable frequency asynchronous motor
2: Synchronous motor
The major difference between ordinary asynchronous motor and variable frequency
Range: 0.00V~10.00V
Range: 0.00V~10.00V
Range: 0.00V~10.00V
Range: 0.00V~10.00V
Reserved
Reserved
Reserved
Reserved
Range: 0~2
- 122 -
E5 User Manual
Factory default:
1.00V
Factory default:
1.00V
Factory default:
9.00V
Factory default:
9.00V
Reserved
Reserved
Reserved
Reserved
Factory default: 0