Chapter 5 Specification of Parameters
Control run command through RUN, STOP/RESET and MF keys on keypad (set
multifunction key MF to JOG by P70.00). Refer to Chapter 3 about the operation of keypad.
1: Terminal control
Control run command via DI terminals. Perform FORWARD and REVERSE by DI terminals.
The control mode are two-wire mode and three-wire mode selectable. See Group P20for
details of designation and wiring regulation of DI terminals.
2: Communication control
Master device is able to control run command through built-in RS485 serial communication
interface of drive. Refer to parameters Group P60 and appendix for further information about
programming.
Run command from keypad, terminals and communication can be switched by terminals "run
command switched to keypad control", "run command switched to terminal control" and "run
command switched to communication control".
Multifunction key MF can be set to "run command sources shifted" key through parameter
P70.00. When MF key is pressed under this setting, run command will be shifted during keypad
control, terminal control and communication control circularly.
Binding of run command
P11.01
and frequency
This parameter defines the bundled combination of three run command sources and frequency
command sources with the purpose of facilitating simultaneous switching.
For example: frequency command source AI1 (unit's place of P11.01 is set to 3) bundled
with keypad control, while the frequency command source X6/DI pulse input (ten's place of
P11.01 is set to 6) bundled with terminal control. In such a case, when run command is
controlled by keypad, frequency command source would be AI1, while when run command is
controlled via terminals, frequency command source will be automatically switched to X6/DI
pulse input.
 Unit's place: frequency command source bundled under keypad control
0: No binding
1: Digital setting (P10.02) + ∧/∨ adjustment on keypad
2: Digital setting (P10.02) + terminal UP/DOWN adjustment
3: Analog input AI1
4:Aanalog input AI2
5: Reserved
6: X6/DI pulse input
7: Process PID output
8: Simple PLC
9: Multi-step frequency
A: Communication input
command
Range: 000 ~ AAA
- 82 -
E5 User Manual
Factory default:
000