0: Positive logic; ON when current passes through
1: Negative logic; ON when no current passes through
 Decade: X6 (same as X5)
 Hundreds place: Reserved
Digital input terminal
P20.16
enabled status setting 3
This parameter sets the enabled condition of AI1, AI2 and EAI as digital input terminal (need to
be defined by P20.08~P20.10).
 Unit's place: AI1
0: Positive logic; < 5V, ON; > 5V, OFF
1: Negative logic; < 5V, OFF; > 5V, ON
 Decade: AI2 (same as AI1)
 Hundreds place: Reserved
Terminal UP/DOWN frequency
P20.17
adjustment treatment
 Unit's place: action when stop
0: Clear
Terminal UP/DOWN frequency adjustment value is cleared when the drive stops.
1: Holding
Terminal UP/DOWN frequency adjustment value is maintained when the drive stops.
 Decade: action on power loss
0: Clear
Terminal UP/DOWN frequency adjustment value is cleared in case of power loss.
1: Holding
Terminal UP/DOWN frequency adjustment value is saved in case of power loss.
 Hundreds place: integral function
0: No integral function
Adjustment step size is kept constant during terminal UP/DOWN adjustment, in compliance
with P20.18.
1: Integral function enabled
When frequency is adjusted through terminal UP/DOWN, initial step size is set by P20.18.
With the effective lasting time of the terminals, adjustment step size will increase gradually.
Terminal UP/DOWN frequency
P20.18
When frequency command is "digital setting + terminal UP/DOWN adjustment", this parameter
is used to set the step size of frequency adjustment UP/DOWN. The step size is defined as
frequency change per second, and the smallest step size is 0.01 Hz/s.
change step size
Chapter 5 Specification of Parameters
Range: 000~111
Range: 000~111
Range:
0.00Hz/s~100.00Hz/s
- 103 -
Factory default:
000
Factory default:
0000
Factory default:
0.03Hz/s