E5 User Manual
Waiting time of auto restart
P11.21
when power up again
This time setting is on the basis of work restoration time of relative devices in the system when
power is up again after power loss, if P11.20 is set to 1.
Group P12 Accel/Decel Parameters
Accel/Decel time
P12.00
0: 0.01s; the setting range of Accel/Decel time is 0.00s~600.00s
1: 0.1s; the setting range of Accel/Decel time is 0.0s~6000.0s
2: 1s; the setting range of Accel/Decel time is 0s~60000s
Accel/Decel time resolution takes effect on P12.01~P12.11.
P12.01
P12.02
P12.03
P12.04
P12.05
P12.06
P12.07
P12.08
These parameters P12.01~P12.08 set the rate of Accel/Decel for speed increase/decrease.
Maximum Freq (P10.08) / Accel time X = Accel Rate X
Maximum Freq (P10.08) / Decel time X = Decel Rate X
As the formula sets forth above, Accel time means required time for drive to Accelerate to
maximum frequency P10.08 from zero frequency, while Decel time refers to the time required
for drive to Decelerate to zero frequency from maximum frequency P10.08.
These four types of Accel/Decel time can be selected through the ON/OFF combination of DI
terminals" Accel/Decel time determinant 1" and " Accel/Decel time determinant 2". See
resolution
Accel time 1
Decel time 1
Accel time 2
Decel time 2
Accel time 3
Decel time 3
Accel time 4
Decel time 4
Chapter 5 Specification of Parameters
Range: 0.0s~10.0s
Range: 0~2
Range: 0s~60000s
Range: 0s~60000s
Range: 0s~60000s
Range: 0s~60000s
Range: 0s~60000s
Range: 0s~60000s
Range: 0s~60000s
Range: 0s~60000s
- 87 -
Factory default:
0.0s
Factory default: 1
Factory default:
6.0s
Factory default:
6.0s
Factory default:
6.0s
Factory default:
6.0s
Factory default:
6.0s
Factory default:
6.0s
Factory default:
6.0s
Factory default:
6.0s