Best E5 Series User Manual page 131

High-performance frequency inverter
Table of Contents

Advertisement

E5 User Manual
Rated
motor
V0, V1, V2, V3 and f0, f1, f2 and f3 in the figure are voltage value and frequency value set by
parameters P31.01~P31.08.
2: 1.2nd power
3: 1.4th power
4: 1.6th power
5: 1.8th power
6: 2.0th power
Parameter values 2~6 apply to torque-dropped loads such as fans and water pumps. See Fig.
6-42.
Rated voltage of motor
7: V/f separated pattern 1
Output frequency and output voltage can be set separately. Frequency is set by the method
as stated in Group 10. Output voltage is set by P31.18. See P31.18 for details. This mode
applies to variable-frequency power supply or torque motor control etc.
8: V/f separated pattern 2
Determine a certain voltage by linear V/f mode, and then multiply this voltage by the
Output voltage (V)
输出电压(V)
电机额定电压
voltage
of
V3
V2
V1
V0
0
f0
Fig. 5-36 User-defined various segments V/f curve
Output voltage (V)
输出电压(V)
1.4次幂
power
1.2次幂
电机额定电压
SL V/f
直线V/f
0
Rated frequency of
Fig. 5-27 1.2~2.0 power V/f curve
f3 电机额定频率
f1
f2
Rated frequency of motor
power
2.0次幂
power
1.8次幂
power
1.6次幂
power
输出频率(Hz)
Output frequency (Hz)
电机额定频率
motor
- 127 -
Chapter 5 Specification of Parameters
Output frequency (Hz)
输出频率(Hz)