Chapter 5 Specification of Parameters
attained" outputs ON signal no matter the drive is set to stop or not stop.
Actual length is saved at power loss and can be read in both stop and running.
P53.12
Set count value
P53.13
Designated count value
The two parameters are used with digital input terminal "count input" and digital output
terminals "set count value attained" and "designated count value attained".
Input pulse through digital input terminal "count input". When the number of pulses attain
the value set by P53.12, the terminal outputs ON. With the completion of the value of P53.12,
the terminal "designated count value attained" outputs OFF.
When the number of input pulses attains the designated count value of P53.13, terminal
"designated count value attained" will output ON. Upon the completion of set count value of
P53.12, terminal "designated count value attained" outputs OFF.
For example: P53.12= 10, P53.13= 7. Fig.5-44:
1
计数输入信号
Count input signal
"指定计数值到"端子
"Designated count value attained" terminal
"设定计数值到"端子
"Set count value attained" terminal
 ATTENTION:
Actual count value can be cleared through digital input terminal "count clear".
Actual count value is saved at power loss.
Group P60 MODBUS Communication Parameters
Support universal Modbus protocol. Please refer to appendix for detailed description of
communication protocol.
P60.00
RS-485 port communication
P60.01
2
3
4
Reserved
configuration
Range: 1~65535
Range: 1~65535
5
6
7
Fig.5-44
Reserved
Range: 000~155
- 164 -
E5 User Manual
Factory default:
1000
Factory default:
1000
8
9
10
11
Reserved
Factory default:
001