Output frequency of drive can normally pass through skip zones during Accel and Decel.
P10.19
Jog frequency
This parameter sets the running frequency during jog. Jog Accel time is set by parameter
P12.10 while its Decel time by parameter P12.11.
Jog run command control could be performed through keypad, control terminals or
communication input.
Multifunction MF key can be set as forward jog or reverse jog key through parameter
P70.00.
Jog can be realized using "forward jog terminal" and "reverse jog terminal" of DI.
Jog can be realized via communication input. See drive communication protocol for further
information.
See Jog diagrammatic sketch Fig. 5-6.
Thereof:
f1 is jog frequency P10.19
t1 represents the ACC time from zero to jog frequency; t1 = (P12.10) ● f1/(P10.08); P10.08
is the maximum frequency.
t2 is the DEC time from jog frequency to 0; t2 = (P12.11) ● f1/(P10.08).
 ATTENTION:
Set value of jog frequency is free from limitations of upper and lower limit frequency.
Jog is started from starting frequency and its start is not subject to limitation by P11.05.
Group 11 Start/Stop Control
P11.00
Run command
This parameter sets run command source. Run commands include "start, stop, forward and
reverse", etc.
0: Keypad control
Range: 0.00Hz ~ upper limit
frequency
运行频率
Running frequency
f1
t1
Fig.5-6
Range: 0~2
- 81 -
Chapter 5 Specification of Parameters
时间
Time
t2
Factory default: 0
Factory default:
5.00Hz