Chapter 5 Specification of Parameters
 ATTENTION:
When Y2/DO terminal is used as high-speed pulse output (set by P23.02), delay time set by
P21.05 is disabled.
Enabled state of digital
P21.08
 Unit's place: Y1
0: Positive logic; ON when current passes through
1: Negative logic; ON when no current passes through
 Decade: Y2 (same as Y1)
 Hundreds place: relay 1 output
0: Positive logic; ON when there is coil excitation
1: Negative logic; ON when there is no coil excitation
 Thousands place: Reserved
Wiring diagram of digital output terminal is shown as Fig. 5-17:
Detected object of frequency
P21.09
doubling technology(FDT)
 Unit's place: FDT1 detective object
0: Set value of speed (frequency after Accel/Decel)
FDT1 output frequency is the command frequency after Accel/Decel.
1: Detected speed value
FDT1 output frequency is actually detected or identified frequency. If the drive is under V/f
pattern, it should be output frequency.
 Decade: FDT2 detective object
0: Set value of speed (frequency after Accel/Decel)
FDT2 output frequency is the command frequency after Accel/Decel.
1: Detected speed value
FDT2 output frequency is actually detected frequency or frequency after autotuning. If the
drive is under V/f pattern, it should be output frequency.
P21.10
FDT1 upper bound
output
Drive
Fig. 5-17
Range: 0.00Hz~maximum FREQ
Range: 0000~1111
Relay
继电器
+24V
Y(i)
(i=1,2)
COM
Range: 00~11
- 110 -
E5 User Manual
Factory default:
0000
Factory default:
00
Factory default:
50.00Hz