Chapter 5 Specification of Parameters
 ATTENTION:
Please set "protection action" with caution since inappropriate setting may extend the fault
Fault memory after power
P41.08
Determine whether or not the previous fault code is to be memorized and displayed upon the
power up of the drive after power loss.
0: Not memorized after power loss
1: Memorized after power loss
 ATTENTION:
Undervoltage fault "LoU" is not memorized after power loss.
P41.09
Times of automatic reset
P41.10
Interval of automatic reset
When a fault occurs during the running, the drive will run at 0Hz with the time set by P41.10,
and then the fault will be reset and the drive continues to run. Times of automatic reset is set by
P41.09. Automatic reset is prohibited and fault protection shall be executed immediately when
P41.09 is set to 0.
 ATTENTION:
1) Automatic fault reset is not performed at the following types of faults:
Module protection "FAL"
Parameter identification failed "tUN"
Current detection abnormal "CtC"
Ground short circuit protection at output side "GdP"
Converter module overload protection "oL3"
Expansion board 1 connection abnormal "EC1"
Expansion board 2 connection abnormal "EC2"
Drive line connection abnormal "dLC"
External equipment error "PEr"
Consecutive running time attained "to2"
Accumulative running time attained fault "to3"
Power supply abnormal during running "SUE"
Parameter copy fault "CPy"
P41.11
Relay action on drive fault
Unit's place: when undervoltage fault occurs
0: No action
loss
Range: 0~1
Range: 0~20
Range: 2.0s~20.0s
Range: 000~111
- 146 -
E5 User Manual
Factory default: 0
Factory default: 0
Factory default:
2.0s
Factory default:
010