Best E5 Series User Manual page 100

High-performance frequency inverter
Table of Contents

Advertisement

Chapter 5 Specification of Parameters
P12.10, and jog Decel time set by P12.11. Refer to P20.00 for enabled conditions on initial
power up.
3: Forward (FWD)
Terminals control forward running of the drive. Refer to P20.00 for enabled conditions on
initial power up.
4: Reverse (REV)
Terminals control reverse running of the drive. Refer to P20.00 for enabled conditions on
initial power up.
5: Three-wire control
There are two-wire control and three-wire control about Forward (FWD) and reverse (REV).
In case of three-wire control is enabled, "three-wire control" terminal is activated. For details,
refer to P20.19 (FWD/REV terminal control mode).
6: Running suspended
When "running suspended" terminal is enabled during the running, the drive will block the
output and perform zero-frequency running. Once "running suspended" terminal becomes
disabled, the drive restores the running.
7: External stop
No matter which type of P11.00 is set to, the drive will stop by enabled "external stop"
terminal, in the manner of stop mode.
8: Emergency stop
When "emergency shutdown" is enabled, the drive will stop in accordance with Decel time
set by P12.09. Please set P12.09 to an appropriate value so as to minimize the Decel time
for emergency stop.
9: Stop command + DC brake
The drive performs ramp-down stop when "stop command+ DC brake" terminal is enabled. It
will perform DC brake when output frequency attains brake starting frequency. Brake starting
frequency and brake current are set by P11.14 and P11.15. Brake time is determined by the
maximum of P11.16 and the lasting time of this terminal.
10: DC brake stop
The drive performs "ramp to stop + DC brake" (same as P11.13 is set to 2) when "DC brake
stop" is enabled, in the manner set by P11.14, P11.15 and P11.16.
11: Coast to stop
When "coast to stop" terminal is enabled, the drive will immediately cut off its output and the
motor will coast to stop.
12: Terminal UP
13: Terminal DOWN
Terminals are used to increase and decrease the command frequency. The command
frequency will be increased and decreased when "digital setting + terminal UP/DOWN
adjustment" is enabled. The adjustment "step size" is set by P20.18. Refer to P20.17 for
Terminal UP/DOWN frequency adjustment treatment.
14: UP/DOWN (including ∧/∨ key) adjustment clear
- 96 -