Chapter 5 Specification of Parameters
2: Stop
If frequency command is lower than lower limit frequency, stop would be activated after the
time delay set by P10.12. When lower limit frequency is 0, this limitation is invalid.
 ATTENTION:
This parameter is disabled under PID control mode.
Time-delay of stop when
P10.12
command frequency lower
than lower limit frequency
When P10.11 is set to 2, and command frequency is lower than lower limit frequency, the drive
will stop running after this parameter value.
Lower limit of skip
P10.13
frequency band 1
Upper limit of skip
P10.14
frequency band 1
Lower limit of skip
P10.15
frequency band 2
Upper limit of skip
P10.16
frequency band 2
Lower limit of skip
P10.17
frequency band 3
Upper limit of skip
P10.18
frequency band 3
Skip frequency is a function designed to prevent the drive running at resonance zone of
mechanical system.
At most 3 skip zones can be defined. See Fig.5-5.
P0.18
P0.17
Once parameters of skip zones are set, the output frequency of the drive would
automatically get out of these skip zones even if the command frequency is within these zones.
Frequency after adjustment
P0.16
P0.15
P0.14
P0.13
Range: 0.0s~6553.5s
Range: 0.00Hz ~ upper limit
frequency
Range: 0.00Hz ~ upper limit
frequency
Range: 0.00Hz ~ upper limit
frequency
Range: 0.00Hz ~ upper limit
frequency
Range: 0.00Hz ~ upper limit
frequency
Range: 0.00Hz ~ upper limit
frequency
Skip frequency band 3
Skip frequency band 2
Skip frequency band 1
Fig.5-5
- 80 -
Factory default:
Factory default:
Factory default:
Factory default:
Factory default:
Factory default:
Factory default:
Command frequency
E5 User Manual
0.0s
0.00Hz
0.00Hz
0.00Hz
0.00Hz
0.00Hz
0.00Hz