Maximum corresponding value
Maximum negative corresponding value
P23.11
DO output filtering time
Set the filtering time of DO high-speed pulse output. Filtering can change the change rate of
output pulse frequency. The longer the filtering time is, the lower the change rate of output
pulse frequency would be.
Group P24 Automatic Correction of Analog Input
Parameter Group P24 is used to perform automatic correction of analog input channels,
obtaining the gain and offset of corresponding channel automatically. They can automatically
modify the measuring range of corresponding channel or correct meter error.
P24.00
Analog corrected channel
0: No correction
No correction to any channels.
1: Correct AI1
Automatically correct analog AI1 channel.
2: Correct AI2
Automatically correct analog AI2 channel.
3: Reserved
Sampling value of
P24.01
calibration point 1 of AI1
Input value of calibration
P24.02
point 1 of AI1
Sampling value of
P24.03
calibration point 2 of AI1
Input value of calibration
P24.04
point 2 of AI1
Corresponding value of DO
0
Fig. 5-33
Range: 0.00V~10.00V
Range: 0.00V~10.00V
Range: 0.00V~10.00V
Range: 0.00V~10.00V
- 121 -
Chapter 5 Specification of Parameters
DO pulse frequency
P23.09
(P23.09)/2
Range: 0.00s~10.00s
Range: 0~3
Factory default:
0.01s
Factory default: 0
Factory default:
1.00V
Factory default:
1.00V
Factory default:
9.00V
Factory default:
9.00V