E5 User Manual
Fault
Fault
code
Display
22
dLC
23
TEr
24
PEr
26
to2
27
to3
28
SUE
29
EPr
30
CCL
Fault
description
board 1
abnormal
connection
Loose or poor expansion
abnormal
board 1 connection
Control board abnormal
Drive board abnormal
Drive line
Loose or poor drive line
connection
connection
abnormal
Control board abnormal
Function
Analog input terminals
conflict of
are set to the same
analog
function
terminals
External fault terminal is
External
enabled
equipment
Stall condition lasts too
error
long
Consecutiv
e running
"Consecutive running
time
time attained" enabled
attained
Cumulative
running
"Cumulative running time
time
attained" enabled
attained
Power
supply
Fluctuation of grid
abnormal at
voltage is out of range
running
EEPROM
Parameter read/write
read/write
abnormal on control
fault
board
Contactor damaged
Contactor
Abnormal contactor
suction
feedback circuit on
fault
control board
Buffer resistance
- 183 -
Chapter 6 Trouble Shooting Easures
Causes
Solutions
Pull out and reinsert
Seek services
Seek services
Pull out and re-insert
after overall
power-down
Seek services
Do not set analog
inputs to the same
function
Check the status of
external fault terminal
Check if the load is
abnormal
See specification of
Group P40
See specification of
Group P40
Check input power grid
voltage
Seek services
Seek services
Seek services
Seek services