B.2
Run-Time Programming Problems
Your program can create non-fatal error conditions (such as addressing errors)
during the normal execution of the program. In this case, the CPU generates a
non-fatal run-time error code. Table B-2 lists the descriptions of the non-fatal error
codes.
Table B-2
Error Code
0000
0001
0002
0003
0004
0005
0006
0007
0008
0009
000A
000B
000C
000D
000E
0091
0092
0094
009A
S7-200 Programmable Controller System Manual
A5E00066097-02
Run-Time Programming Problems
Run-Time Programming Problem (Non-Fatal)
No error
HSC box enabled before executing HDEF box
Conflicting assignment of input interrupt to a point already assigned to a
HSC
Conflicting assignment of inputs to an HSC already assigned to input
interrupt or other HSC
Attempted execution of ENI, DISI, SPA, or HDEF instructions in an interrupt
routine
Attempted execution of a second HSC/PLS with the same number before
completing the first (HSC/PLS in an interrupt routine conflicts with HSC/PLS
in main program)
Indirect addressing error
TODW (Time-of-Day Write) or TODR (Time-of-Day Read) data error
Maximum user subroutine nesting level exceeded
Execution of a XMT or RCV instruction while a different XMT or RCV
instruction is in progress on Port 0
Attempt to redefine a HSC by executing another HDEF instruction for the
same HSC
Simultaneous execution of XMT/RCV instructions on Port 1
Clock cartridge not present
Attempt to redefine pulse output while it is active
Number of PTO profile segment was set to 0
Range error (with address information): check the operand ranges
Error in count field of an instruction (with count information): verify the
maximum count size
Range error writing to non-volatile memory with address information
Attempt to switch to freeport mode while in a user interrupt
Error Codes
B-3