Table A-5 Noise Suppression Codes Of Analog Input Modules - Siemens SIMATIC S7-300 Manual

Automation system, module data
Hide thumbs Also See for SIMATIC S7-300:
Table of Contents

Advertisement

Parameter sets of signal modules
A.4 Parameters of analog input modules
Noise suppression
The table below contains the coding at byte 1 of data record 1 for the various frequencies
(see the previous figure.) Make allowances for the resultant integration time at each channel!
Table A-5
Noise suppression codes of analog input modules
Noise suppression
400 Hz
60 Hz
50 Hz
10 Hz
Measuring methods and ranges
The table below shows all measuring methods and ranges of the analog input module,
including their codes. Enter these codes at bytes 2 to 5 in data record 1 (refer to the previous
figure.)
Note
You may have to reposition a measuring range module of the analog input module to suit the
measuring range.
Table A-6
Measuring range codes of analog input modules
Measuring method
disabled
Voltage
4-wire transducer
2-wire transducer
A-8
Code
Measuring range
2#0000
disabled
2#0001
± 80 mV
± 250 mV
± 500 mV
± 1 V
± 2.5 V
± 5 V
1 V to 5 V
0 V to 10 V
± 10 V
± 25 mV
± 50 mV
2#0010
± 3.2 mA
± 10 mA
0 mA to 20 mA
4 mA to 20 mA
± 20 mA
± 5 mA
2#0011
4 mA to 20 mA
Integration time
2.5 ms
16.7 ms
20 ms
100 ms
S7-300 Automation System Module data
Manual, 08/2006, A5E00105505-04
Code
2#00
2#01
2#10
2#11
Code
2#0000
2#0001
2#0010
2#0011
2#0100
2#0101
2#0110
2#0111
2#1000
2#1001
2#1010
2#1011
2#0000
2#0001
2#0010
2#0011
2#0100
2#0101
2#0011