Input Response Time Setting - Mitsubishi Electric L02SCPU User's Manual And Reference

Melsec-l series, cpu module
Table of Contents

Advertisement

3.8

Input Response Time Setting

This function changes the input response time for each input module. Input modules obtain external inputs within the
set response time.
For the input response time setting by the built-in I/O function, refer to the following.
MELSEC-L CPU Module User's Manual (Built-In I/O Function)
(1) Setting procedure
1.
Select "Input" under "Type" in the I/O Assignment tab, and click the
Project Window  [Parameter]  [PLC Parameter]  [I/O Assignment]
2.
Select any of the following values for "I/O Response Time". (Default: 10ms)
1ms, 5ms, 10ms, 20ms, 70ms
The shorter the input response time is, the more the CPU module is susceptible to noise. Consider the operating
environment when setting input response time values.
102
ON
OFF
External input
OFF
Input module
Input response time
ON
button.