RADWAG WLY User Manual page 136

Y series
Hide thumbs Also See for WLY:
Table of Contents

Advertisement

The condition is marked with signal flags, which determine formulation making
process between the weighing platforms, in a way which orders dosing Water
ingredient as the second one. The whole process is described below in
tables, separately for each weighing platform.
Dosing process name: Instance 2
Dosing process code: 2222
Dosing process from a terminal level:
Platform 1
Icon
Step
1. [CM] Weight
condition
2. [Z] Zero
3. [TI] Delay
4. [DA] Automatic
batching
5. [TI] Delay
6. [O] Outputs
7. [F] Set flags
Dosing on the first weighing platform is carried out in two-steps, as for
ingredient „Flour" the outputs are set for two-step dosing – see Products
database.
Value
Description
Condition checking, unless the weighing
Gross<0.1 kg
platform is loaded with a mass exceeding
100 g
Zero
Zeroing the weighing platform no. 1
[5s] Open
Pending for opening main valve of the
valve Flour
container with "Flour"
Automatic dosing of product „Flour" to
obtain 1 kg mass in bulk dosing mode
(bulk dosing and fine dosing valves are
1,2 kg [Flour]
opened – Outputs 1 and 2), and 0,2 kg
mass is dosed using fine dosing valve only
–fine dosing valve is opened on Output 1
(for two-step dosing process)
[3s] Close
Pending for closing the main valve of the
valve „Flour "
container "Flour"
Output 11 takes high status („1") – signal
confirming carrying out the dosing making
Output 11 – „1"
process on the weighing platform no. 1 is
lit up
Setting the characteristic point of the
Signal flag 1 –
process, which is a condition for carrying
„1"
out part of the process on the second
weighing platform
136

Advertisement

Table of Contents
loading

This manual is also suitable for:

Wpy

Table of Contents