Default Parameters; Ekip Touch Default Parameters - ABB SACE Emax E1.2 Operating Instructions For The Design Engineer

Sace emax 2 series low voltage air circuit-breakers
Hide thumbs Also See for SACE Emax E1.2:
Table of Contents

Advertisement

22 - Default parameters

Ekip Touch default parameters The Ekip Touch trip units are supplied with the following default parameters:
129 | © 2017 ABB | 1SDH001330R0002 - ECN000058721 Rev. A
Protection/Parameter
L
S
(2)
I
G
(2)
2I
MCR
IU
OT
I1 current thresholds
Current thresholds
Harmonic Distortion
Gext
(2) (3)
Rc
(3)
Frequency
Neutral
Datalogger
Power Controller
Hardware Trip
Monitor time
Local Bus
Alive LED
Language
Password
Mode
Modbus RTU par
Profibus
DeviceNet™
Modbus TCP/IP
Maintenance
(1)
Thermal memory, startup, Zone Selectivity set to Off.
(2)
S Protection available with LSI and LSIG versions of the trip unit. G Protection available with LSIG version.
(3)
Protections available if the respective toroids (S.G.R. or Rc) are present.
(4)
Protection activated on request when purchasing the trip unit.
The protections activated by the presence of the Ekip Measuring Pro module, have the following default
parameters:
Protection/Parameter
VU
UV
OV
UF
OF
RP
Phase Sequence
Cos φ
Value
(1)
1 In; 144 s; pre-alarm: 90 %
Off; 2 In; 50 ms; Curve: t = k
4 In
Off; 0.2 In; 400 ms; Curve: t = k
Off; 1.5 In
Off; 6 In; 40 ms
Off; 50%; 5 s
Off
Off; 1: 50 %; 2: 75 %
Off; Iw1: 3 In; Iw2: 3 In
On
Off; 0.2 In; 400 ms; Curve: t = k
Off; 3 A; 60 ms
50 Hz (IEC) / 60 Hz (UL)
Off (for circuit breakers three-pole)
50 % (for four-pole circuit-breaker)
Off
See note
(4)
Disabled
5 minutes
Disabled
Disabled
English
00001
Local
Address: 247; baudrate: 19.2 Kbit/s
Address: 125
MAC ID: 63; baudrate: 125 Kbit/s
Static IP: 0.0.0.0
Off
Value
Off; 50%; 5 s
Off; 0.9 Un; 5 s
Off; 1.05 Un; 5 s
Off; 0.9 fn; 3 s
Off; 1.1 fn; 3 s
Off; 0.1 Sn; 10 s
1-2-3
Off; 0.95
ABB | SACE Emax 2
Continued on the next page
Ekip Touch protection trip unit | 22 - Default parameters

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sace emax e2.2Sace emax e4.2Sace emax e6.2

Table of Contents