Technical Characteristics; Protection Degree; Dissipated Power - ABB SACE Emax E1.2 Operating Instructions For The Design Engineer

Sace emax 2 series low voltage air circuit-breakers
Hide thumbs Also See for SACE Emax E1.2:
Table of Contents

Advertisement

8 - Technical characteristics

Protection degree SACE Emax 2 circuit-breakers guarantee the following protection degrees:
Dissipated power To guarantee the performance of the switchgear in terms of uninterrupted rated capacity, the design of the
290 | © 2017 ABB | 1SDH001330R0002 - ECN000058721 Rev. A
• IP20 for circuit-breakers in fixed or withdrawable versions, excluding the terminals
• IP30 for the front parts of the circuit-breaker when it is installed in a switchboard with IP30 flange mounted
on the door
• IP54 in circuit-breakers equipped with an optional IP54 transparent flange fitted to the front door of the
switchboard.
switchgear must take into account the power dissipated by switchgear and controlgear and by the installed
live parts. Dissipated powers are calculated according to the standard IEC 60947. The values indicated in
the table refer to the total power for each three-phase circuit-breaker with balanced loads with a current flow
equal to the rated uninterrupted current Iu. These power dissipations are measured according to the standard
IEC 60947. The values indicated in the table refer to the total power of the circuit-breakers in three-pole and
four-pole versions with balanced loads and a current flow equal to the rated uninterrupted current Iu at 50/60
Hz.
Dissipated power [W]
Iu
E1.2 B/C/N
F
W
(1)
(2)
630A
31
62
800A
50
100
1000A
78
156
1250A
122
244
1600A
201
400
2000A
2500A
3200A
4000A
5000A
6300A
Dissipated power [W]
E1.2
E2.2
Iu
B/N/S - A
B/N/S - A
F
W
F
(1)
(2)
(1)
250A
7
14
400A
17
35
15
800A
59
118
48
1200A
125 250
100 152
1600A
170 260
2000A
2500A
3200A
3600A
4000A
5000A
(1)
Fisso - Fixed - Fest - Fixe - Fijo
(2)
Estraibile - Withdrawable - Ausfahrbarer - Débrochable - Extraíble
E2.2 B/N/S/H
E4.2 N/S/H/V
F
W
F
(1)
(2)
34
72
53
113
83
176
136
288
212
450
267
550
425
465
E2.2 H/V - A
E4.2
E2.2 2000A
S/H/V - A
B/N/S - A
W
F
W
F
W
(2)
(1)
(2)
(1)
22
15
22
73
48
68
44
58
99
138
86
114
167 233
143 189
250 350
211 279
310 410
E6.2 H/V/X
W
F
(1)
(2)
(1)
743
900
309
483
767
E4.2 L - A
E6.2
E4.2 3200A
H/V - A
S/H/V - A
F
W
F
W
(2)
(1)
(2)
(1)
(2)
42
49
81
111
132 181
193 264
280 384
445 610
323 438
395 536
476 646
700 950
Mechanical accessories | 8 - Technical characteristics
ABB | SACE Emax 2
W
(2)
544
850
1350
E6.2 L - A
F
W
(1)
(2)
476 646
700 950

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sace emax e2.2Sace emax e4.2Sace emax e6.2

Table of Contents