Ekip Com Profinet Modules; Description; Compatibility And Power Supply - ABB SACE Emax E1.2 Operating Instructions For The Design Engineer

Sace emax 2 series low voltage air circuit-breakers
Hide thumbs Also See for SACE Emax E1.2:
Table of Contents

Advertisement

11 - Ekip Com Profinet modules

Description The Ekip Com Profinet is a communication accessory module, that integrates the circuit-breaker in an
Compatibility and power supply The modules can be installed combined with Ekip Touch, Hi-Touch, G Touch, and G Hi-Touch trip units, and
225 | © 2017 ABB | 1SDH001330R0002 - ECN000058721 Rev. A
industrial remote supervision and control network.
It can be connected to an Ethernet network with a Profinet communication protocol, and allows you to:
• Connect the trip units to the network, with dialog functionality.
• Command opening and closing of the circuit-breaker from remote.
• Provide information on the state of the circuit-breaker (open, closed, tripped).
• If mounted on a circuit-breaker in withdrawable version, detect the connected/disconnected position.
For more details about how to access information and transmit commands to the trip unit via the module,
consult chapter "System Interface" on page 155.
Remote opening and closing of the circuit-breaker can be performed only if the circuit-breaker is equipped
with an Ekip Com Actuator module (see page 243).
IMPORTANT: the module can only be connected to networks that meet all the necessary
requirements for security and prevention of unauthorized access (for example, the
network of the control system of an installation). It is the installer's responsibility to
ensure that all the necessary security measures are adopted (for example, firewalls,
and so on). Connection to dedicated Ethernet networks through Profinet communication
protocol is recommended. The module cannot be connected to the Internet.
The following table shows the ports used by the module:
Ethertype
Port
0x88CC.
-
0x8892 (Profinet).
-
0x0800.
34964/udp
For applications in which a high network reliability is necessary, the module can be installed along with the
corresponding Redundant module.
The Redundant module is identical in terms of characteristics and installation, but its wiring is different from
the non-Redundant model.
IMPORTANT: on each circuit-breaker, only one Ekip Com Profinet, and only one Ekip
Com Profinet Redundant can be installed.
IMPORTANT: when the circuit-breaker is in the disconnected position, the trip unit
is disconnected from the module: in this condition, the only valid information
transmitted is:
• Connection of trip unit to Com module (Trip unit disconnected = disconnected).
• CB position (CB isolated / CB connected = CB isolated).
• Presence of com module ( = present; only valid for the module to which it is connected).
Further details are given in document
Interface for Emax 2), sections Status Global 1 [dlog], Status Accessories 1 and
Status Accessories 2.
The modules are always supplied with Ekip AUP and Ekip RTC contacts (see the chapter "16 - Other
accessories" on page 244).
require the presence of an Ekip Supply module in the first slot of the circuit-breaker terminal box.
Service
LLDP
Profinet IO
Profinet-cm (Context Manager)
1SDH001140r0001
Electronic accessories | 11 - Ekip Com Profinet modules
ABB | SACE Emax 2
Notes
Link Layer Discovery Protocol
Specific for real time
communications (RT)
DCE/RPC