ABB SACE Emax E1.2 Operating Instructions For The Design Engineer page 136

Sace emax 2 series low voltage air circuit-breakers
Hide thumbs Also See for SACE Emax E1.2:
Table of Contents

Advertisement

130 | © 2017 ABB | 1SDH001330R0002 - ECN000058721 Rev. A
Continued from the previous page
The Ekip Hi-Touch and Ekip G Hi-Touch trip units have additional protections, provided with the following
default parameters:
Protection/Parameter
S2
D
UV2
OV2
UF2
OF2
Network Analyzer
Harmonic calculation
Set A-B
The Ekip G Touch and Ekip G Hi-Touch trip units have additional protections, provided with the following
default parameters:
Protection/Parameter
S(V)
RV
RQ
OQ
OP
UP
The Ekip G Hi-Touch trip units has additional protections, provided with the following default parameters:
Protection/Parameter
ROCOF
S2(V)
RQ2
Value
(1)
Off; 2 In; 50 ms; Curve: t = k
Off; 2 In; 200 ms
Off; 0.9 Un; 5 s
Off; 1.05 Un; 5 s
Off; 0.9 fn; 3 s
Off; 1.1 fn; 3 s
Off
Off
Off
Value
(1)
Off; type = step; 1 In; UI = 1 Un; Ks = 0.6; t20 = 1 s
Off; 0.15 Un; 15 s
Off; Kq = -2; Q24 = 0.1 An
Off; 1 Sn; 1 s
Off; 1 Sn; 1 s
Off; 1 Sn; 1 s
Value
Off; 0.6 Hz; 500 ms
Off; type = step; 1 In; UI2 = 1 Un; Ks2 = 0.6; t21 = 1 s
Off; Kq = -2; Kq2 = 2; Q24 = 0.1 Sn; Q25 = 0.11 Sn; Vmin = 0.5 Un; 100 s
Ekip Touch protection trip unit | 22 - Default parameters
ABB | SACE Emax 2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sace emax e2.2Sace emax e4.2Sace emax e6.2

Table of Contents