Advertisement

280 | © 2017 ABB | 1SDH001330R0002 - ECN000058721 Rev. A
Continued from the previous page
5.
Turn the crank clockwise until the pushbutton comes out and the indicator shows that the circuit-
breaker is in TEST position. See Figure 84.
Figure 84
6.
Press the lock button and then rotate the crank clockwise until the button comes out and the indicator
shows that the circuit-breaker is in the CONNECT position. See Figure 85.
Figure 85
7.
Extract the crank. See Figure 86.
8.
Replace the crank in its housing See Figure 87.
Figure 86
2
Figure 87
ABB | SACE Emax 2
1
Continued on the next page
Mechanical accessories | 5 - Operating mode for E1.2