Programmable functions It is possible to program eight commands, with automatic activation based on signals or events.
System In the menu Settings - System some system parameters are available:
Maintenance The Maintenance function allows the user to be alerted by a Warning alarm that:
125 | © 2017 ABB | 1SDH001330R0002 - ECN000058721 Rev. A
The commands are:
Command type
Trip
Change protection set (from Set A to Set B)
Change configuration (from Remote to Local)
Reset the contacts of the signalling modules
Opening coil command (YO).
Closing coil command (YC).
Reset energy counters
Reset of the trip signal
Each command provides two programming parameters:
• Activation function: event or events (up to eight, in logical AND or OR configuration) that activate the
command.
• Delay: command sending delay, calculated starting from the occurrence of the activation event.
NOTE: the command is sent if the event is present for a time greater than the delay that has
been set.
NOTE: the YO and YC commands are possible only if the coils are present and if all the
operating conditions exist (circuit-breaker open).
Date, to set the current date.
Time, to set the current time
Language, to set the language of the menus.
Password, in order to reconfigure the password.
NOTE: the date and time are maintained thanks to an internal battery in the trip unit. In the
event of date and time fault, you are advised to follow the procedure for replacement of the
battery.
• One year has passed since the last maintenance.
• Contact wear has increased by more than 10% compared with the value at the last maintenance.
There are two areas available on the display:
• Activation area (Main page - Menus - Settings - Maintenance): it allows the maintenance function to be
activated.
• Measurements and reset area (Main page - Menus - Measurements - Maintenance): it appears only if the
maintenance function is activated; it provides information related to maintenance (contact wear and dates)
and the command for confirming that maintenance has been carried out (by confirming, the current date
and contact wear values are recorded, and the alarm signal is reset).
The reference date is that of the internal clock, and the elapsed time is calculated both with the trip unit on
and off (provided that the internal battery is working).
NOTE: manual modification of the date can cause variations in the calculation of the time
elapsed, and therefore in the date of the next maintenance.
NOTE: the maintenance signal due to increased contact wear is active for values higher than
20 %.
Path
Advanced - Functions
Advanced - Functions
Settings - Modules - Functions
Settings - Modules - Functions
Settings - Functions
Settings - Functions
Measurements - Energies - Function
Advanced - Functions
Ekip Touch protection trip unit | 21 - Additional Ekip Touch functions