Electrical Accessories; Electrical Control Accessories; Yo-Yc-Yo2-Yc2 (1) : Opening And Closing Coil - ABB SACE Emax E1.2 Operating Instructions For The Design Engineer

Sace emax 2 series low voltage air circuit-breakers
Hide thumbs Also See for SACE Emax E1.2:
Table of Contents

Advertisement

Electrical accessories

1 - Electrical control accessories

YO-YC-YO2-YC2
: Opening
(1)
and closing coil
249 | © 2017 ABB | 1SDH001330R0002 - ECN000058721 Rev. A
The opening coils, YO and YO2, and the closing coil, YC and YC2
remotely.
The opening of the circuit-breaker is always possible with the circuit-breaker closed, while closing is possible
with the circuit-breaker open and the closing springs charged.
The opening and closing coils can operate in two different modes:
• instantaneous service (the minimum duration of the command impulse must be 100 ms).
• service with permanent power supply.
YO-YC-YO2 for E1.2
YO-YC-YO2-YC2 for E2.2 - E4.2 - E6.2
NOTE: the second opening coil YO2 is alternative to the undervoltage coil YU.
IMPORTANT:
• If the closing coil is permanently energized and the opening coil trips, after opening,
the closing coil must be momentarily de-energized so that it can be reused for the next
closing operation.
• If instead the opening coil trips, it is necessary, after having de-energized it, to wait at
least 100 ms before operating the closing coil.
Available voltages and characteristics
The tables listing the available voltages and the electrical characteristics are provided below:
Available voltages (Un)
24 V AC/DC
30 V AC/DC
48 V AC/DC
60 V AC/DC
110...120 V AC/DC
220...240 V AC/DC
240...250 V AC/DC
277 V AC/DC
380...400 V AC
415...440 V AC
480...500 V AC
500...550 V AC
(1)
YC2 not available for E1.2
(1)
D1
C1
C11
C3
C13
D2
C2
C12
YU
YC
YO
YO 2
D1
C1
C11
C21
C3
C13
D2
C2
C12
C22
YU
YC
YO YC 2
YO 2
General characteristics
Operating limits
Inrush power (Ps)
Continuous power (Pc)
Maximum opening time
Maximum closing time
Electrical accessories | 1 - Electrical control accessories
ABB | SACE Emax 2
, allow the circuit-breaker to be controlled
YO-YO2
YC-YC2
70...110 %Un
85...110 %Un
300 VA/W
3.5 VA/W
35 ms
-
-
50 ms
Continued on the next page
(1)

Hide quick links: