About Menu This menu allows you to view information on:
Measurements Menu This menu allows you to:
51 | © 2017 ABB | 1SDH001330R0002 - ECN000058721 Rev. A
• Mainboard and trip unit (serial number, model, software version, etc.).
• The circuit-breaker (serial number, rated current, configuration with or without neutral, number of poles,
fixed or withdrawable version, state, etc).
• The connected electronic accessories (serial number, model if present, software version if present,
information on state if present, etc).
• Date and time.
Function
Information
It displays:
Protection unit
• Information on Mainboard and trip unit.
• Date and time.
Circuit Breaker
Displays information on the circuit-breaker.
Modules
It displays a list of the electronic accessories connected.
• Load input status: shows the Open/Closed state of the loads
Power Controller
(1)
• Load Active: shows the Active/Inactive state of the loads.
(1)
Menus available with the Power Controller function enabled (see the Settings Menu- Power Controller).
• It open lists of recorded events.
• It display measurements in graphical or numerical form.
• It reset measurements.
The following table shows the submenus and the parameters associated to the menu Measurements up
to Level 3 (if present), and the Ekip Touch trip units where they can be found. The options corresponding
to parameters and commands are underlined, to distinguish them from those corresponding to submenus.
Options
Measurements
• Trip: it opens a list of the trip performed.
• Events: it opens a list of the recorded events.
Historicals
• Measurements: it opens a list of the dimensions whose history can
be displayed.
Power factor
It displays the power factor measured.
Frequency
It shows the frequency measured for the voltages.
• Energy counters: it displays the active, reactive and apparent
energies measured.
• Reset counters: it resets the energy counters.
Energy
• Energy RESET: opens a list of the parameters for programming the
reset of the energy counters (see the chapter "20 - Operating features",
and the paragraph "Functional characteristics", on page 124).
It shows the peak factors measured for the phase currents and the
Peak factor
neutral currents.
It opens the Modify Parameters page, to enable/disable the alarm
Harmonic
Distortion
with a peak factor greater than 2.1.
Ekip
It opens a list of the measurements related to the synchronism
Synchrocheck
function.
(2)
• V Sequences: it shows the last and penultimate positive and
negative voltage sequences measured.
• V 3s Sequences: it shows the voltage sequences and unbalance
measured in last the 3 seconds.
• THD Current: it shows the measurements of the harmonic
Network
distortion of currents.
Analyzer
• THD Voltages: it shows the measurements of the harmonic
(3)
distortion of line-to-line voltages.
• Counters: it allows you to display the number of events monitored
by the function in the last twenty-four hours and the totals.
• Waveforms: it opens a list of the currents and voltages for which an
instantaneous wave form can be displayed.
ABB | SACE Emax 2
Trip units
Touch
G-Touch
Hi-Touch
G Hi-Touch
Touch
(1)
G-Touch
Hi-Touch
G Hi-Touch
Touch
G-Touch
Hi-Touch
G Hi-Touch
Touch
(1)
G-Touch
Hi-Touch
G Hi-Touch
Hi-Touch
G Hi-Touch
Continued on the next page
Ekip Touch protection trip unit | 6 - Menu