Hi-Touch Measurements; Presentation; Waveforms; Harmonics - ABB SACE Emax E1.2 Operating Instructions For The Design Engineer

Sace emax 2 series low voltage air circuit-breakers
Hide thumbs Also See for SACE Emax E1.2:
Table of Contents

Advertisement

17 - Hi-Touch measurements

Presentation Hi-Touch measurements are available for Ekip Hi-Touch and Ekip G Hi-Touch trip units.
Waveforms Path
Harmonics Path
Network Analyzer Path
114 | © 2017 ABB | 1SDH001330R0002 - ECN000058721 Rev. A
IMPORTANT: the measurements are available with trip units equipped with auxiliary
power supply.
The following is a list of the available measurements:
Measurements
Description

Waveforms

Display of the waveforms of the voltage and current signals and current

Harmonics

Display of the harmonic component of the voltage and current signals

Network Analyzer

Statistical analysis of voltages and currents
Main page - Menu - Measurement - Network Analyzer - Waveforms
Description
The selection of one of the listed quantities opens the representation of the waveform of the selected quantity
acquired at the moment of selection.
The quantities with which the waveform can be displayed are:
• Phase currents L1, L2, L3, Of.
• Line-to-line voltages V12, V23, V31.
NOTE:
• The Ne phase current is available with four-pole or three-pole circuit-breakers with external
neutral.
• For details on the pages, see the chapter "Menu Page and menus", and the paragraph
"Measurements Menu", on page 51.
Main page - Menu - Measurement - Network Analyzer - Waveforms
Description
In the above mentioned page, the Harmonics key opens a representation in the form of a histogram of the
measurements of the harmonics constituting the waveform, and related to the frequency set in the menu
Settings.
In order to display the harmonics, you need to enable the calculation of the harmonics through the parameter
Harmonic, available in the menu Measurements.
NOTE: For details on the pages, see the chapter "Menu Page and menus", and the paragraph
"Measurements Menu", on page 51.
Main page - Menu - Measurements - Network Analyzer (for the measurements and the counters)
Main page - Menu - Settings - Network Analyzer (for the control parameters)
Description
The Network Analyzer function allows you to set voltage and current controls over a long period, in order to
analyze your system.
To this purpose, voltages and currents are monitored, so as to find:
• Voltage sequences.
• Short voltage sags or interruptions.
• Short voltage increases.
• Slow voltage sags.
• Slow voltage increases.
• Unbalances between the voltages.
• Harmonic distortion of voltages and currents.
Continued on the next page
Ekip Touch protection trip unit | 17 - Hi-Touch measurements
ABB | SACE Emax 2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sace emax e2.2Sace emax e4.2Sace emax e6.2

Table of Contents