Ekip Measuring Measurements; Presentation; Instantaneous Voltages - ABB SACE Emax E1.2 Operating Instructions For The Design Engineer

Sace emax 2 series low voltage air circuit-breakers
Hide thumbs Also See for SACE Emax E1.2:
Table of Contents

Advertisement

16 - Ekip Measuring Measurements

Presentation These measurements are available in all the models of trip units of the Ekip TOUCH range supplied with Ekip
Instantaneous voltages Description
110 | © 2017 ABB | 1SDH001330R0002 - ECN000058721 Rev. A
Measuring module or Ekip Measuring Pro.
The following is a list of the available measurements:
Measurements
Description
Instantaneous voltages Real Time measurements of the voltages
Instantaneous power
Real Time measurements of the active, reactive, apparent power
Trips
List of the trips due to voltage, frequency, power
Maximum voltage
History of the maximum voltages recorded with an interval that can be set
Minimum voltage
History of the minimum voltages recorded with an interval that can be set
Maximum power
History of the maximum active powers recorded with an interval that can be set
Average power
History of the average active powers recorded with an interval that can be set
Power factor
Real time measurement of the power factor
Instantaneous
Measurement of the line frequency
frequency
Energy counters
Measurement of active, reactive, apparent energy
With the Ekip Measuring Pro module and Ekip Synchrocheck, a further set of measurements is activated:
Measurements
Description
Measurements related to the function of synchronism between two
Synchrocheck
independent power supply systems
Power references
Displayed operating ranges and maximum values of power described in this chapter are given in absolute
value or in relation to:
• Pn for the total power (Sn = In * Un * √3).
• Pn for the phase power (Pn = In * Un / √3).
Instantaneous voltages are measurements in real time of the line-to-line and phase voltages.
NOTE: the measurements of the phase voltages are available with four-pole or three-pole
circuit-breakers configured with external neutral.
Representations and access pages
Voltage measurements are available in different representations, accessible from the following pages:
• In the Histograms page there is a graphical representation in the form of a histogram of the line-to-line
voltages, and the measurement in Volts of the highest voltage.
• In the Measurements Synthesis page, accessible from the Histograms page, there is the measurement
in Volts of the highest line-to-line voltage.
• In the Measuring instruments page there is a graphical representation in the form of a voltmeter and
measurement in Volts of the highest line-to-line voltage.
• In the Measurements page there are measurements in Volts of all the line-to-line voltages and phase
voltages.
The measurements in Volts are available from a minimum value of 5 V to a maximum value of 1.25 Un.
NOTE:
• "..." is displayed, for voltage values lower than 5 V, "> 1.25 Un" is displayed for voltage values
greater than 1.25Un (example: with Un = 100 V, "> 125 V" is displayed).
• In the Histograms page, the graphical representation of the voltages relates to 1 Un, with a
maximum value of 1.25