Aux 15Q: External Additional Open/Closed Auxiliary Contacts - ABB SACE Emax E1.2 Operating Instructions For The Design Engineer

Sace emax 2 series low voltage air circuit-breakers
Hide thumbs Also See for SACE Emax E1.2:
Table of Contents

Advertisement

AUX 15Q: External additional
open/closed auxiliary contacts
255 | © 2017 ABB | 1SDH001330R0002 - ECN000058721 Rev. A
The additional AUX 6Q contacts signal the open/closed state of the circuit-breaker.
These are "switching" contacts and are available in two types:
• 15 standard contacts
• 15 digital signals (low power)
The following table provides information on the electrical characteristics:
Characteristics
DC
Breaking capacity
AC
Minimum load
AUX 15Q Connections
Further information is available on page 174, or on the website http://www.abb.com/abblibrary/
DownloadCenter/, where the wiring diagram is available 1SDm000091r0001.
Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/,
in particular for E1.2 in the kit sheet
1SDH001000r0607.
Standard
24V
-
125V
0.5A @ 0ms / 0.3A @ 10ms
250V
0.3A @ 0ms / 0.15A @ 10ms
3A cos φ 0.3
250V
5A cos φ 0.7
5A cos φ 1
3A cos φ 1
400V
2A cos φ 0.7
1A cos φ 0.3
100mA @ 24V
1SDH000999r0607
ABB | SACE Emax 2
Digital signals
0.1 A
-
-
-
-
-
-
-
-
1mA @ 5V
and for E2.2-E4.2-E6.2 in the kit sheet
Electrical accessories | 2 - Electrical signalling accessories