Connections; Cs And Tc Connection Check; Connection Of Current Sensor For External Neutral; Default Parameters - ABB Tmax T7 Operating Instructions Manual

T7-t8-x1 low voltage air circuit breakers protection releases
Hide thumbs Also See for Tmax T7:
Table of Contents

Advertisement

2.6.2.

Connections

WARNING: Strict compliance with the instructions given in this document is required for the connections at the
user's charge.
This will ensure compliance with all the international reference standards and guarantee that the protection
release functions perfectly even in heavy duty environmental and electromagnetic conditions. Pay particular
attention to the earth connection.
2.6.3.

CS and TC connection check

WARNING: If the PR331/P has been installed by the user, remember to check (with the CB open and Vaux or
PR030/B), prior to putting the circuit-breaker into service, to make sure that the CS and TC cables have been
connected correctly. Make the correct connections if this is not the case. If all the red leds come on, it means
that there is an error in the CS and/or TC connections
2.6.4.

Connection of current sensor for external neutral

WARNING: Remember to set the InN in the appropriate way if the current sensor for the external neutral conduc-
tor must be connected to a three-pole circuit-breaker.
During this phase, the circuit-breaker must be open and, if possible, isolated.

2.7. Default parameters

Before the PR331/P is put into service, it is essential for the user to define and carefully adjust the editable parameters to suit
his installation requirements.
ABB will apply the adhesive rating plates of all the variables concerning the CB (e.g. Type of CB, Rating Plug size, etc.) so as to
provide the user with all the information he needs to define the parameters.
PR331/P is supplied with the following predefined parameters:
#
Protection
1
L
2
S
3
I
4
G
5
Mains frequency
6
Neutral sel
7
S51/P1
Note:
(1) = 50 Hz for IEC type CB
60 Hz for UL type CB
(2) = Off for three-pole CB
50% for four-pole CB
B0431
Model
Threshold
1 In
Off
4 In
Off
50 Hz
(1)
(2)
Alarm L
B1751
Time
144 s
0,1 s
--
0,1 s
0 s
Apparatus
Emax X1-Tmax T7-Tmax T8
1SDH000587R0002
Doc. No
Scale
Page No
17/66