3 - Mechanical Interlocks

Mechanical interlock of type A -
Two Circuit-breakers
Mechanical interlock of type B -
Three Circuit-breakers
1 2 3
O
I
O
I
O
Mechanical interlock of type C -
Three Circuit-breakers
1 2 3
O
I
O
O
O
I
I
Mechanical interlock of type D -
Three Circuit-breakers
1 2 3
O
I
O
O
267 | © 2017 ABB | 1SDH001330R0002 - ECN000058721 Rev. A
Mechanical interlocks determine the opening/closing logic between two or three circuit-breakers.
Four types of interlocks are available, usable in both fixed and withdrawable versions.
The Type A interlock is applicable to two circuit-breakers (normal power supply + emergency power supply).
It allows you never to have two circuit-breakers in the closed position at the same time.
1 2
Information on assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/, in
particular with the kit sheets:
O
O
1SDH000999r0720
I
O
1SDH001000r0720
O
I
1SDH000999r0721
The Type B interlock is applicable to three circuit-breakers (two normal power supplies + emergency power
supply).
It only allows the closing of the two circuit-breakers of the normal power supply if the circuit-breaker of the
emergency power supply is open. The circuit-breaker of the emergency power supply can be closed only if
O O
the others two are open.
O
O
Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/, in
O
I
particular with the kit sheet 1SDH001000r0721.
O
I
I
O
The Type C interlock is applicable to three circuit-breakers (two normal power supplies + a bus tie).
It allows the simultaneous closing of one or two circuit-breakers, resulting in two possible types of power
supply of the half busbars:
• power supply from a single transformer (bus tie closed)
O O
• power supply from both transformers (bus tie open)
O
O
I
O
Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/, in
O
I
particular with the kit sheet 1SDH001000r0722.
I
I
I
O
O
I
The Type C interlock is applicable to three circuit-breakers (three power supplies on the same bar that must
not operate in parallel)
It allows only one of the three circuit-breakers to be closed.
Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/, in
O O
particular with the kit sheet 1SDH001000r0723.
O
O
I
O
O
I
for interlock between E1.2circuit-breakers
for interlock between E2.2-E4.2-E6.2 circuit-breakers
for interlock between one E1.2 circuit-breaker and one E2.2-E4.2-E6.2 circuit-breaker
ABB | SACE Emax 2
Mechanical accessories | 3 - Mechanical Interlocks