Access from the display With the modules energized, and the Local Bus enabled, the presence of the modules on the terminal box
211 | © 2017 ABB | 1SDH001330R0002 - ECN000058721 Rev. A
activates additional menus on the display.
To enable the Local Bus, you need to select "On" in the menu Settings - Modules - Local Bus.
The following table shows the path for accessing the configuration parameters of the modules from the
display:
...
Main frequency
Settings
Modules
Power Controller
...
(1)
As Ekip Com Modbus RTU.
The following table shows the configuration parameters of the modules:
Parameter Values
Default
• Ekip Com Modbus
Serial
RTU: 247
1... 247
address
• Ekip Com Modbus
RTU Redundant: 246
9600 bit/s,
Baudrate
19200 bit/s,
19200 bit/s
38400 bit/s
Physical
8.E,1, 8.O,1,
8,E,1
protocol
8.N,2, 8.N,1
NOTE: the modules can also be configured with the Ekip Connect software (see the chapter
"16 - Other accessories", and the paragraph "Ekip Connect software" on page 245).
The following table shows the path from the display for accessing information on the modules:
Protection Unit
Circuit-breaker
About
Modules
Power Controller
The information on the modules that can be displayed includes the serial number and the software version.
Local/Remote
Local Bus
...
Ekip Com Modbus RTU
Ekip Com Modbus RTU *R
...
Functions
Description
Address to be assigned to the modules.
IMPORTANT: devices connected to
the same network must have different
addresses.
Data transmission speed
• 8.E,1 = 8 data bits, 1 EVEN parity bit, 1 STOP bit.
• 8.O,1 = 8 data bits, 1 ODD parity bit, 1 STOP bit.
• 8.N,2 = 8 data bits, no parity bit, 2 STOP bits.
• 8.N,1 = 8 data bits, no parity bit, 1 STOP bit.
...
Ekip Com Modbus RTU
Ekip Com Modbus RTU *R
...
Electronic accessories | 7 - Ekip Com Modbus RTU modules
ABB | SACE Emax 2
Serial address
Baudrate
Physical
protocol
(1)