Access from the display With the modules energized, and the Local Bus enabled, the presence of the modules on the terminal box
230 | © 2017 ABB | 1SDH001330R0002 - ECN000058721 Rev. A
Continued from the previous page
For the communication bus, a cable of type Cat.6 S/FTP must be used (Cat.6 with S/FTP double shielding).
If the circuit-breaker is in withdrawable version, the use of cables fitted with a RJ45 socket with output at 90°
is recommended.
Further information is available on page 174, or on the website http://www.abb.com/abblibrary/
DownloadCenter/, where the wiring diagram is available 1SDm000091r0001.
activates additional menus on the display:
• To set the addressing of the modules.
• In order to display information on the modules.
To enable the Local Bus, you need to select "On" in the menu Settings - Modules - Local Bus.
The following table shows the path from the display, for setting the function and addressing of the modules:
...
Main frequency
Settings
Modules
Power Controller
...
(1)
As Ekip Com EtherNet/IP™.
The following table shows the parameters for setting the function and the addressing of the modules. For
further information, see the table on page 223.
Parameter
Selectable values
Force Static IP
Off, On
address
Displayed with static IP Address enabled, it must be selected in order to insert the IP
Static IP Address
Address of the modules.
Static Network
Displayed with static IP Address enabled, it must be selected in order to insert the
Mask
subnet mask of the modules.
Displayed with static IP Address enabled, it must be selected in the presence of
Static Gateway
multiple subnets, in order to insert the IP Address of the node to which the modules
addr
are connected.
Local/Remote
Local Bus
...
Ekip Com EtherNet/IP™
Ekip Com EtherNet/IP™ *R
...
Functions
Default
Description
• Off = Dynamic IP address.
Off
• On = Static IP address.
Electronic accessories | 12 - Ekip Com EtherNet/IP™ modules
ABB | SACE Emax 2
Force Static IP address
Static IP Address
Static Network Mask
Static Gateway addr
(1)
Continued on the next page