Summary table of Hi-Touch protections

ABB
ANSI
Threshold
(4)
I5 = 0.6...10 In
S2
50 TD
step = 0.1 In
I7 Fw/Bw = 0.6...10 In
D
67
step = 0.1 In
U15= 0.5....0.98 Un
UV2
27
step = 0.001 Un
U16= 1.02....1.5 Un
OV2
59
step = 0.001 Un
f17= 0.9....0.999 fn
UF2
81L
step = 0.001 fn
f18= 1.001....1.1 fn
OF2
81H
step = 0.001 fn

Table of Additional functions of the protections

The following table summarises the additional functions combined with protections S2 and D:
ABB
ANSI
Threshold
(4)
S2
I5
= 0.6...10 In
-
startup
(Startup)
step = 0.1 In
S2
68
-
(Sdz)
D
I7
= 0.6...10 In
-
startup
(Startup)
step = 0.1 In
D
68
-
(SdZ)
(1)
Calculation of t
is valid for values exceeding the tripping threshold of the protection.
t
(2)
Valid tolerances with steady-state energized trip unit or trip unit energized by auxiliary power supply, tripping time ≥ 100 ms, temperature and
currents within operating limits. If these conditions are not guaranteed, the tripping time tolerance of ± 10 % will become ± 20%.
(3)
For the startup functions, the specified time is the period during which the protection with the different threshold remains active, calculated from the
moment the startup threshold is exceeded.
(4)
ANSI / IEEE C37-2 encoding.
(5)
Valid tolerance for frequencies in the range: fn ± 2 %. For frequency outside the range a tolerance of ± 5 % applies.
89 | © 2017 ABB | 1SDH001330R0002 - ECN000058721 Rev. A
Tolerance
Time
threshold
± 7 % If ≤ 6 In
t5 = 0.05...0.8 s
± 10 % If > 6 In
step = 0.01 s
± 7 % If ≤ 6 In
t7 Fw/Bw = 0.1...0.8 s
± 10 % If > 6 In
step = 0.01 s
t15 = 0.05...120 s
± 2 %
step = 0.01 s
t16 = 0.05...120 s
± 2 %
step = 0.01 s
t17 = 0.15...300 s
± 1 %
(5)
step = 0.01 s
t18 = 015...300 s
± 1 %
(5)
step = 0.01 s
Threshold
Time
tolerance
(2)
± 7 % with If ≤ 6 In
t5
startup
± 10 % with If > 6 In
step = 0.01 s
t2
= 0.04...0.2 s
-
sdz
step = 0.01 s
t7
± 10 %
startup
step = 0.01 s
t7
-
SdZ
step = 0.01 s
Calculation
formula t
t
= t5
t
t
= t7
t
t
= t15
t
t
= t16
t
t
= t17
t
t
= t18
t
Calculation
(3)
formula t
= 0.1...30 s
t
= t5
t
startup
-
= 0.1...30 s
t
= t7
t
startup
= 0.1...0.8 s
-
Ekip Touch protection trip unit | 11 - Hi-Touch protections
ABB | SACE Emax 2
Tolerance t
(2)
(1)
t
t
The better of the two values:
± 10 % or ± 40 ms
The better of the two values:
± 10 % or ± 40 ms
The better of the two values:
± 10 % or ± 40 ms (for a time
set < 5 s) / ± 100 ms (for a time
set > 5 s)
The better of the two values:
± 10 % or ± 40 ms (for a time
set < 5 s) / ± 100 ms (for a time
set > 5 s)
The better of the two values:
± 10 % (min=30ms) or ± 40 ms
(for a time set < 5 s) / ± 100 ms
(for a time set > 5 s)
The better of the two values:
± 10 % or ± 40 ms (for a time
set < 5 s) / ± 100 ms (for a time
set > 5 s)
Tolerance t
(2)
(1)
t
t
The better of the two values:
± 10 % or ± 40 ms
-
The better of the two values:
± 10 % or ± 40 ms
-