Access From The Display - ABB SACE Emax E1.2 Operating Instructions For The Design Engineer

Sace emax 2 series low voltage air circuit-breakers
Hide thumbs Also See for SACE Emax E1.2:
Table of Contents

Advertisement

Access from the display With the modules energized, and the Local Bus enabled, the presence of the modules on the terminal box
222 | © 2017 ABB | 1SDH001330R0002 - ECN000058721 Rev. A
Continued from the previous page
For the communication bus, a cable of type Cat.6 S/FTP must be used (Cat.6 with S/FTP double shielding).
If the circuit-breaker is in withdrawable version, the use of cables fitted with a RJ45 socket with output at 90°
is recommended.
Further information is available on page 174, or on the website http://www.abb.com/abblibrary/
DownloadCenter/, where the wiring diagram is available 1SDm000091r0001.
activates additional menus on the display:
• For setting the function and addressing of the modules.
• In order to display information on the modules.
To enable the Local Bus, you need to select "On" in the menu Settings - Modules - Local Bus.
The following table shows the path from the display, for setting the function and addressing of the modules:
...
Main
frequency
Settings
Modules
Power
Controller
...
(1)
As Ekip Com Modbus TCP menu.
The following table shows the parameters for setting the function and the addressing of the modules. For
further information, see the table on page 223.
Selectable
Parameter
values
HTTP Server,
Function
Modbus TCP
Force Static IP
Off, On
address
Static IP
Displayed with static IP Address enabled, it must be selected in order to insert the IP
Address
Address of the modules.
Static Network
Displayed with static IP Address enabled, it must be selected in order to insert the subnet
Mask
mask of the modules.
Displayed with static IP Address enabled, it must be selected in the presence of
Static Gateway
multiple subnets, in order to insert the IP Address of the node to which the modules are
addr
connected.
Local/Remote
Local Bus
...
Ekip Com Modbus TCP
Ekip Com Modbus TCP *R
...
Functions
Default
Description
• HTTP Server = HTTP Server operating mode.
Modbus TCP
• Modbus TCP = Communication module operating
mode.
• Off = Dynamic IP address.
Off
• On = Static IP address.
Electronic accessories | 10 - Ekip Com Modbus TCP modules
ABB | SACE Emax 2
Function
Force Static IP address
Static IP Address
Static Network Mask
Static Gateway addr
(1)
Continued on the next page