16 - Other accessories

Ekip LCD The LCD version of the protection trip unit can be requested for installations in particularly aggressive
Rating Plug The Rating Plug defines the rated current In necessary to set the current protections on the trip unit, since
Toroid S.G.R. S.G.R., or Source Ground Return, is the external homopolar current sensor that can be installed with the
Rc Toroid Rc is the external residual current sensor, that can be installed with Ekip Touch, Hi‐Touch, G Touch, and G
244 | © 2017 ABB | 1SDH001330R0002 - ECN000058721 Rev. A
environments (low temperatures, high degree of humidity, dust or chemical substances). The LCD version
differs from the version with touchscreen display in:
• Black and white LCD display.
• Menu navigation by buttons.
• The HOME button provides direct access to the page Menu. The Measurements pages can be accessed
using the ARROW UP and ARROW DOWN buttons from the page Histograms. (Main Page and Measuring
Instruments area are not available).
All the protection, measurement and accessory options are the same as those of the touchscreen version.
these refer to In.
It is supplied with all Ekip trip units, mounted on a front connector dedicated and accessible to the user, and
can be replaced with trip unit off and circuit breaker open.
IMPORTANT: the replacement of the Rating Plug with trip unit on or circuit breaker
closed may cause malfunction of the trip unit, or unwanted opening of the circuit-
breaker.
NOTE: a trip unit can be equipped with any Rating Plug with a maximum rated current equal
to Iu, i.e. the rated uninterrupted current of the circuit-breaker (indicated on the rating plate
of the circuit-breaker).
The trip unit continuously checks for the presence of the Rating Plug, signalling its absence or any assembly
or installation errors.
Once mounted, when the trip unit is energized, its installation is requested.
To activate the residual current protection on the Touch, Hi-Touch, G Touch and G Hi-Touch trip units, it is
necessary to mount a Rating Plug Rc. Rating Plug L = OFF, which allow you to deactivate the protection L
are also available.
Further details about assembly and the Rating Plug installation procedure are available on the website http://
www.abb.com/abblibrary/DownloadCenter/, in particular in the kit sheet 1SDH001000r0510.
following trip units: Ekip Touch, Hi-Touch, G Touch, and G Hi-Touch, LSIG version.
During the programming of the trip unit, the presence of the toroid S.G.R. must be selected in the menu
Settings - Circuit-breakers - Ground Protection in order to activate the protection against ground fault
(Gext) (see the menu Advanced).
IMPORTANT: the S.G.R. Toroid can be selected as an alternative to the Rc type.
Therefore Gext and Rc protections are alternatives.
Further information on the connection of the S.G.R. toroid is available on the website http://www.abb.com/
abblibrary/DownloadCenter/, in particular in kit sheet 1SDH001000r0507.
Hi-Touch trip units equipped with Rating Plug Rc, Ekip Measuring Pro and Ekip Supply modules.
During the programming of the trip unit, the presence of the RC toroid must be selected in the menu Settings
- Circuit-breakers - Ground Protection in order to activate the RC protection (see the menu Advanced).
IMPORTANT: the Rc toroid can be selected as an alternative to the S.G.R type.
Therefore the Rc and Gext protections are alternatives.
Further information on the connection of the Rc toroid is available on the website http://www.abb.com/
abblibrary/DownloadCenter/, in particular in kit sheet 1SDH001000r0521.
ABB | SACE Emax 2
Electronic accessories | 16 - Other accessories